Fire Alarm Control Panel 6/8 Loop

The FireNET™ 6127/8127 control panel is an analog addressable fire alarm panel containing 6/ 8 SLC loops with each loop supporting 127 devices of any combination (sensors or modules), and 127 analog sounder bases, for a possible total of 254 points. Communication between devices is transferred through standard cable (shielded or twisted pair is not required). Each panel includes two 5.25 amp power supplies and has 8 on board NAC circuits. An RS-485 bus provides communication to the panel network, while the two RS-232 interface allows the convenience of programming via a PC. The system will support a variety of Hochiki devices: photo, ion and heat sensors, which contain a unique, patented sensor design incorporating automatic drift compensation and day/night sensitivity mode. Additional devices include contact monitors, relay controllers, supervised auxiliary output and short circuit isolator modules. In addition, interfaces to conventional detection systems can be established by using a conventional zone-monitoring module. The Loop Explorer Windows® Software interface provides the installer with fingertip access to installation programming and diagnostic tools. AnAuto-learn feature offers the convenience for quick start applications. Add to this a reputation for high quality and dedicated service makes this an exceptional product both in performance and value.

· Analog design using Hochiki’s advanced DCP protocol for fast and robust communication

· Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop

· Uses standard wire, no shielded or twisted pair required on SLC loops · Supports Class B (style 4) and Class A (style 6 or 7) SLC loops

· 8 on board Class B (style Y) NAC circuits rated at 2.5 Amp each

· Programmable sensitivity levels per device & automatic day/night sensitivity modes

· Automatic daily calibration & drift compensation routine

· Large 8-line x 40-character LCD display (320 char.)

· 8 loop version (1600 addresses/sub-addr. max.)

· Dual RS-485 bus for panel network

· 2 built-in RS-232 interfaces for programming via a PCand two serial printer interfaces

· 10 on board programmable Form C relays rated at 1 amp at 30VDC (Fire1, Fire2, trouble, supervisory, aux.) x 2

· 1000mA of auxiliary power available rated at 24 VDC

· Loop Explorer Windows® configuration utility

· *500 network wide software zones

· Network Capbility of up to 64 panels

· Two RS485 slave bus for expansion - up to 64 FN-4127- IO boards or up to 35 FN-LCD-S serial annunciators and/ or up to 32 FN-4127-IO boards per bus

· Auto-learn feature

· Built in help and alarm information screens

· Fire Drill test function

· Walk Test function

· Alarm Verification feature

· Operates on 120VAC or 240VAC input voltage

· Powerful & versatile Cause & Effect programming (up to · 500 maximum, network wide) including: *Cause & Effect action *Disable function configuration *Test mode configuration

Primary AC 120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 50hz
Output DC 24VDC @ 5.25 Amps (4 Amps availble for system power)
Power Supply (2) 5.25Amp integrated
Charger Current 1.5 Amps max, per power supply
Dimensions 29"W x 24" H x 5"D
Weight Approx. 60 lbs (without batteries)
Material ABS/steel, enclosure Red (optional charcoal)
Display 8 line x 40 character LCD (320 characters total)
Network Dual RS485 ports (64 panels max.)
Zones 500 network wide software zones per system
SLC loops 4 or 8 (class A, "style 6 or 7" or class B, "style 4")
Devices per loop 127 sensors & modules, plus 127 analog sounder bases, 254 total
Addresses per panel (1600 addresses+sub-addresses max. per panel)
NAC Outputs (8) 2.5 Amp @ 24VDC (class B)
Relay Outputs (10) Form C 1Amp @ 30VDC
Voltage Outputs (6) 500mA @ 24VDC
Aux. Power 1000mA @ 24VDC
Aux. Inputs (16) digital pull downs
PC Port RS232
Printer Port RS232

 